    "act_title": "The Bombay Lifts Rules, 1958",
    "act_slug": "the-bombay-lifts-rules-1958",
    "section_label": "Section",
    "section": {
        "number": "25",
        "title": "25. Operation and Operating Device.",
        "chapter": null,
        "content": "(b) With D. C. power supplies, the disconnecting switch and any circuit breaker shall be so arranged that the brake circuit is opened at the same time that the main circuit is opened.\n(c) The interruption of the electrical circuit shall stop or shall prevent the movement of the car.\n(d) No control shall depend upon the completion or maintenance of an electric circuit for -\n(i) the interruption of the power supply to the motor and the application of the brake to stop the lift-car at terminal landings or to stop the lift-car when the emergency stop switch is operated;\n(ii) the operation of the safety gear ;\n(e) Control circuit shall be so arranged that an earth fault or open circuit shall not create an unsafe condition.\n(f) Automatic (push button operated) lifts shall conform to the following requirements :-\n(i) [* * *]\n(ii) Automatic lifts which travel at a speed over [0.75m./sec.] per minute shall automatically slow down to a speed of [0.75m./sec.] per minute when making a stop at any landing.\n(iii) In the case of an automatic lift, no operation of a spring nor the completion of another electric circuit shall be depended upon to break the circuit to stop the lift at terminal landings.\n(iv) The landing push buttons shall be inoperative during the whole time an occupied lift-car is in use. The landing push buttons shall remain inoperative until the person or persons using the lift have vacated the lift-car and the landing gear or door has been again close, except that in cases where a preselector circuit is used, the push buttons may be utilised for this purpose, provided they do not in any way interfere with the direction of the current journey and that a time lag is provided to regulate the restarting of the lift-car.\n(v) If a movable floor construction is used in the lift-car the entire floor within the car enclosure shall be movable and shall operate when a weight of [14 kg.] is placed upon it at any point.\n(vi) No handrail or seat shall be fitted in the lift-car with movable floor construction.\n[(g)) Every automatically controlled lift-car and every lift-car having a lift-car levelling device shall be provided with emergency stopping device operated by a push buttons switch in the car and it shall be clearly marked in red.]\n(h) An emergency stop switch, of manually opened and closed type, shall be provided on the top of every lift-car and in the lift pit and shall be marked conspicuously.\n(i) Drum drive machine shall not be used for speeds exceeding [0.5 m./ sec.] per minute.\n(j) All lifts travelling at a speed of [1 m./sec.] per minute and over shall be provided with an approved floor levelling device.\n(k) Signal bells or similar apparatus which can be operated from any floor in conjunction with an indicator in the lift-car, shall be provided on all lifts operated by lift operators.\n(l) When more than one operating device is used in a lift-car, the operating devices shall be so interlocked that only one device is effective at a time.\n[(m) The operation of the fire lift in building having more than 24 metres height, shall be a simple toggle or two button switch situated in a glass fronted box adjacent to the lift at entrance level on ground floor. When the switch is 'ON', the landing call points shall become inoperative and car shall report to the ground floor and the same shall remain on car control only. When the switch is 'OFF', the lift shall return to normal working.]",
        "footnote": "",
        "is_definition": false,
        "sort_order": 32
    },
    "prev_section": "24",
    "next_section": "26"
}