    "act_title": "The Assam Factories Rules, 1950",
    "act_slug": "the-assam-factories-rules-1950-1950",
    "section_label": "Section",
    "section": {
        "number": "28",
        "title": "28. How to introduce steam for humidification.",
        "chapter": null,
        "content": "(a) the diameter of such pipes shall not exceed two inches and in the case of pipes installed after 1st day of November, 1950 the diameter shall not exceed one inch ;\n(b) such pipes shall be as short as is reasonably practicable ;\n(c) all hangers supporting such pipes shall be separated from the bare pipes by an efficient insulator not less than half an inch in thickness;\n(d) no uncovered jet from such pipe shall project more than 4-½ inches beyond the our surface of any cover ;\n(e) the steam pressure shall be as low as practicable and shall not exceed 70 lbs per square inch ;\n(f) the pipe employed for the introduction of steam into the air in a department shall be effectively covered with such non-conducting material, as may be approved by the Inspector in order to minimise the amount of heat radiated by them into the department.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 31
    },
    "prev_section": "27",
    "next_section": "29"
}