    "act_title": "Tamil Nadu Combined Development and Building Rules, 2019",
    "act_slug": "tamil-nadu-combined-development-and-building-rules-2019",
    "section_label": "Section",
    "section": {
        "number": "53",
        "title": "53. Exit Requirements.",
        "chapter": null,
        "content": "(a) Every building meant for human occupancy shall be provided with exits sufficient to permit safe movement and also escape of occupants in case of fire or other emergency.\n(b) All exits shall be free of obstructions.\n(c) No building shall be altered so as to reduce the number, width or portion of exits to less than required.\n(d) Exits shall be clearly visible and the routes to reach exits shall be clearly marked and signs posted to guide the occupants of floor concerned.\n(e) All exit ways shall be properly illuminated.\n(f) Fire fighting equipment where provided along exits shall be suitably located and clearly marked but must not obstruct the exit way and there should be clear indication about its location from either side of the exit way.\n(g) Alarm devices shall be installed to ensure prompt evacuation of the occupants concerned through the exits, wherever required.\n(h) All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street.\n(i) Exits shall be so arranged that they may be reached without passing through another occupied unit, except in the case of residential buildings.\nTypes of Exits.\n(b) Lifts, escalators and revolving doors shall not be considered as exits.\nNumber and size of Exits.\nArrangement of Exits.\n(b) The travel distance to an exit from the dead end of a corridor shall not exceed half the distance as stated above except in the case of institutional occupancy in which case it shall not exceed 6m.\nPassenger elevators or lifts.\n(b) Every lift shall be in conformity with the following requirements:\n(i) The lift way and the car shall be enclosed.\n(ii) The lift shaft shall be enclosed with fire resisting materials and shall be ventilated from the highest point direct to the open air.\n(iii) The motors, the winding gear and the operating mechanism shall be installed in a chamber constructed of fire resisting materials and shall be ventilated from the highest point direct to the open air.\n(iv) These shall be fitted with an inter-locking device of such a type as will prevent,\n(a) all landing doors, other than the door to be opening at which the lift car is at rest, from being opened and\n(b) the car being moved until all doors, including the car door, are closed.\n(v) Precautionary measures shall be adopted to ensure the safety of passengers in the event of:-\n(a) an interruption or failure of electric supply;\n(b) a defect or failure in the controlling mechanism;\n(c) the rupture or displacement of ropes or shelves;\n(d) over running or excessive speed of the lift-car due to electrical or other defects in the motor or other mechanism;\n(e) the loading of the car in excess of its maximum capacity; and\n(f) articles falling upon the lift.\n(vi) The safe carrying capacity of the lift or elevator shall be conspicuously posted in or on the car or platform.\n(vii) Every lift shall be properly lighted.\n(viii) Once in every year, lift shall be got inspected and certified by a competent Engineer\n(c) For requirements regarding planning, designing and installation, etc. of lifts and escalators, reference shall be made to the NBC Part 8 'Building Services Section 5 Installation of Lifts and Escalators'.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 59
    },
    "prev_section": "52",
    "next_section": "54"
}