    "act_title": "Delhi Electricity Regulatory Commission (State Grid Code) Regulations, 2008",
    "act_slug": "delhi-electricity-regulatory-commission-state-grid-code-regulations-2008",
    "section_label": "Section",
    "section": {
        "number": "29",
        "title": "29. Event Information.",
        "chapter": null,
        "content": "(a) Violation of security standards;\n(b) Grid indiscipline;\n(c) Non-compliance of the SLDC's instructions;\n(d) System is landing/system split;\n(e) Black out/partial system black out;\n(f) Protection failure on any element of STS;\n(g) Power system instability; and\n(h) Tripping of any element of the State Grid.\n(a) Time and date of Event;\n(b) Location;\n(c) Plant and/or Equipment directly involved;\n(d) Description and cause of Event;\n(e) Antecedent conditions;\n(f) Demand and/or Generation (in MW) interrupted and duration of interruption;\n(g) All relevant system data including copies of records of all recording instruments including Disturbance Recorder, Event Logger and Data Acquisition System;\n(h) Sequence of trippings with time;\n(i) Details of Relay Flags; and\n(j) Remedial measures.\nChapter V\nScheduling and Despatch Code",
        "footnote": "",
        "is_definition": false,
        "sort_order": 28
    },
    "prev_section": "28",
    "next_section": "30"
}