    "act_title": "Cuttack Development Authority (Planning and Building Standards) Regulations, 2001",
    "act_slug": "cuttack-development-authority-planning-and-building-standards-regulations-2001",
    "section_label": "Section",
    "section": {
        "number": "55",
        "title": "55. Bathrooms and water closets.",
        "chapter": null,
        "content": "(a) be so situated that at least one of its walls shall open to external air and shall have a minimum opening in the form of window or ventilation to the extent of 0.37 square metre;\n(b) not be directly over or under any room other than another latrine, washing place, bath or terrace unless it has a water tight floor;\n(c) have the platform or seat made of water tight, non absorbent material;\n(d) be enclosed by walls or partitions and the surface of every such wall or partition shall be finishing with a smooth impervious material to a height of not less than 1 metre above the floor of such room, and\n(e) be provided with an impervious floor covering sloping towards the drain with suitable grade and not towards verandah or any; other room.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 54
    },
    "prev_section": "54",
    "next_section": "56"
}